Code Compliance
Code compliance for PPS sites ranges from Fire to Building, Electrical, and Mechanical codes, among others. Some of the most critical safety work in our schools is to maintain continual compliance with the Fire Code.
Maintaining Fire Code compliance is the responsibility of each site supervisor with the support of their Senior Facility Operations Manager and PPS Operations. The PPS Code Compliance Manager is the liaison who works directly with the Portland Fire Marshal and will be on site to observe site inspection activities with them.
This form from Portland Fire and Rescue shows the most common safety violations in classrooms. For easy reference, it is posted in every school.
MOVING OR CHANGING THE USE OF A CLASSROOM OR SPACE?
A permit from the City of Portland is required for approval to change the use of a room. Site administrators should contact Real Estate & Construction if they would like to request a change of space use. If a space use is changed without a permit, it may be reverted back to the original use in order to align with code requirements.
FIRE / EARTHQUAKE DRILLS:
All site administrators must maintain current fire and earthquake drill documentation in the red “Fire & Life Safety” book located in the office. Schools enrolled in the K-2 on the Second Floor Program must perform fire drills weekly through September.
CLASSROOMS & CORRIDORS:
Help keep PPS in compliance with the Fire Code by always doing the following:
CORRIDORS & STAIRWELLS:
Do not locate combustible (paper and fabric) displays in stairwells. Maintain corridors and stairwells free-and-clear of objects that could obstruct emergency egress. Cross-corridor displays and banners are prohibited.
STOREROOMS:
Maintain 24-inch aisles throughout all storerooms. Maintain a minimum 24-inch clearance between the top of storage items and the ceiling. Maintain 24-inch clear pathway to fire-fighting equipment such as fire extinguishers and fire sprinkler valves and fire alarm panels. Stored items on the top shelves should not exceed 18-inches in height. Maintain at least an 18-inch clearance between the top of all stored items and overhead sprinklers.
BOILER ROOMS:
Boiler rooms are required to be maintained in a clean orderly fashion. Boiler rooms are not allowed to be used for any storage. Combustible materials such as paper and cardboard are strictly prohibited in boiler rooms. Flammable liquids must be stored in flammable liquid cabinets with doors closed and latched at all times. A clear area of 36 inches from electrical panels or equipment disconnects is required. Grease or oil-laden rags used for cleaning oil filters must be placed in an approved metal type 1 flammable material disposal container. Containers are red with self-closing lid. Call Herb Wagner ext. 74277 for disposal.
ELECTRICAL DISTRIBUTION, MDF AND HDF ROOMS:
Storage is not allowed in MDF and HDF rooms. No items may be placed within 36 inches of electrical panels or equipment disconnects.
ELECTRICAL SUB DISTRIBUTION PANELS: (Located in custodial closets, storerooms and corridors)
Clearance of 36 inches of electrical sub-distribution panels is required. Panels located in corridors and stairwells should be closed and locked at all times. Maintain a 24-inch clear pathway to fire-fighting equipment such as fire extinguishers and fire sprinkler valves. No storage shelving may be placed in front of fire-fighting equipment.
MECHANICAL ROOMS & FAN ROOMS:
Storage is not allowed in mechanical rooms, fan rooms, plenums or elevator equipment rooms. Clearance of 36 inches of equipment disconnects is required. Maintain 24-inch clear pathway to fire-fighting equipment such as fire extinguishers and fire sprinkler valves.
MISCELLANEOUS:
Fire extinguishers, fire hose cabinets and fire alarm pull stations are to remain unobstructed, with access free and clear at all times.